FLUE GAS MEASURING DEVICE


With its capability to perform both basic, or more complex flue gas analysis, maintenance or safety checks, or confirm furnace efficiency, the fully featured combustion analyzer delivers more combustion parameters. The stainless steel probe and cone-stop is perfect for residential, and boiler applications. The 310 can be used for accurate heating adjustments, so you can get it right the first time - every time. With five different fuels to select from (Natural Gas, Propane, Fuel Oil 2, Biomass 5%, Wood 20%), it provides the flexibility you need for your tuning opportunities. With an optional printer kit available, you are able to keep records of all readings taken.

Measures:

  • O2, CO (with built-in NOx filter), CO2
  • Undiluted CO (CO air free)
  • Ambient CO
  • Draft & Pressure
  • Temperature (flue & ambient)
Combustion/flue gas efficiency & excess air

What’s included:  Combustion analyzer, lithium battery, sensors, probe with cone, hose, silicon tubing (for pressure), extra particulate filters (5), AC power supply (USB), pressure plugs (5), calibration certificate, & case.



Technical data

Technical data

Storage temperature

-4° to 122 °F (-20 to +50°C)

Operating temperature

23° to 113 °F (-5 to +45°C)

Dimensions

7.9 x 3.2 x 1.7 in.

Differential pressure

Technical data

Measuring range

-16.06 to 16.06 inH2O (-40 to 40 hPa)

Accuracy

0.2 inH2O (± 0.5 hPa)

Resolution

0.01 inH2O (0.1 hPa)

O measurement (electrochemical)

Technical data

Measuring range

0 to 21 Vol. %

Accuracy

±0.2 Vol. %

Resolution

0.1 Vol. %

Exhaust gas measurement

Technical data

Measuring range

0 to 99.9%

Resolution

0.1%

Typ J (FeCuNi)

Technical data

Measuring range

0 to +400 °C

Accuracy

±1 °

Reaction time

< 50 sec.

Draft measurement

Technical data

Measuring range

-8.03 to 8.03 inH2O (-20.00 to 20.00 hPa)

Accuracy

0.01 inH2O (-0.01 to 0.01 inH2O) (± 0.03hPa (-39.00 to 3.00 hPa)) ±1.5% of rdg. (remaining range)

Resolution

0.001 inH2O (0.01 hPa)

CO

Technical data

Measuring range

0 to 4000 ppm

Accuracy

±20 ppm (0 to 400 ppm)
±5% of rdg. (401 to 2000 ppm)
±10% of rdg. (2001 to 4000 ppm)

Resolution

1 ppm

Reaction time

60 sec.

Typ K

Technical data

Measuring range

-4 to 212 °F (-20 to +100 °C)

Accuracy

±1 °C

Resolution

0.1 °C

Reaction time

< 50 sec.

Efficiency Measurement (Eta)

Technical data

Measuring range

0 to 120 %

Resolution

0.1%